        Product Model:HMI1011-MBus


        Function Description:

  HMI1011-MBus can convert MBus to BACnet, with 1 Ethernet Port, 1 RS485 Port, 1 MBus Port.

         Gateway can connect 2-Wire and 4-Wire MBus meter to Building control configuration software such as Johnson¡®s Metasys, Honeywell¡¯s EBI or Niagara, Siemens' Insight or Desigo CC, Schneider's EBO, etc. Also can connect MBus meter to traditional configuration software such ad Citect, IFIX, RSVIEW, WinCC, KingView, Force Control etc.

        Supported devices include MBus water meter, MBus energy meter, MBus heat meter, and Modbus devices.
       
        This product is to replace the original XR1005-MBUS concentrator with a WEB configuration gateway. MBus concentrator and gateway functions are integrated into one device, there is no need to install two devices, which is convenient for customers to wire, saves installation space, and saves costs. The gateway is configured by X2View software, without configuration function. It can also support personal WeChat Alarm, enterprise WeChat Alarm, DingTalk Alarm, MQTT server (supporting Sunfull Cloud platform and FanNeng Cloud platform), project upload cloud and other functions.

         Users can configure the project based on the on-site device list and forward it to a standard BACnet IP, Modbus RTU/TCP server. Upload to the hardware gateway, and BACnet/Modbus clients can access the data of on site devices through the gateway. (Note: The Modbus register of the gateway collection end starts with a decimal address of 1 (Base1) and a hexadecimal address of 0 (Base0).)

 

 Collection Model:

       1¡¢MBus_WaterMeter
      
 2¡¢MBus_EnergyMeter
       3¡¢MBus_EnergyMeter_EN

     
  4¡¢ModbusRTUClient  
       5¡¢ModbusTCPClient
       6¡¢DL/T645-1997/2007       
       7¡¢Simulator


      Note:

      1. 2-Wire MBus device can only be connected to the M+ and M- terminals of COM1 port, with a voltage of around 36V; 4-wire MBus device can be connected to COM2. The A+ and B - terminals have a voltage within 5V. Connecting them in reverse can burn the gateway or meter, and any consequences caused by wiring issues are the responsibility of the customer Undertake.

      2. COM2 is a standard RS485 port that can be used to connect devices with Modbus RTU protocol, while the Ethernet port can connect devices with Modbus TCP protocol.

      3. When connecting a 2-wire MBus device, must use a 24V power supply.
 
      4. Customers encounter non-standard MBus protocols that support paid custom development, which can generally be completed within 3 working days.


      Runtime environment:

      OS£º Win7¡¢Win8¡¢Win10¡¢ Win11¡¢Win Server 2008¡¢Win Server 2016

      The hardware gateway comes with a built-in web server that supports browsers such as Google Chrome, Microsoft Edge, Apple Safari, Firefox, Opera, and 360 Speed Mode.


      Register Type&Num

      The number of gateway registers is dynamically supported, and 512 points can be built for each     

BACnet Register Type

BACnet Register Number

AI(Read Only)

512

AO(R&W)

512

AV(R&W)

512

BI(Read Only)

512

BO(R&W)

512

BV(R&W)

512

MSI(Read Only)

512

MSO(R&W)

512

MSV(R&W)

512

 

 Modbus Register Type

       Modbus Register Number     

 0X(Coil Status, R&W)

512

 1X(Input Status,Read Only )

512

 4X(Holding Register, R&W)

512

 3X(Input Register, Read Only)

512

      Note: 4X and 3X register addresses = transfer addresses *2+1
                 0X and 1X Register address = transfer address +1



Software Features£º

- BTL Certificate and Bacnet International corporate GoldMember;
- Support convert MBus_WaterMeter(CJ188), MBus_EnergyMeter(CJ188), MBus_EnergyMeter_EN, ModbusRTUClient, ModbusTCPClient, DLT645-1977, DLT645-2007 to BACnet IP, Modbus RTU/TCP, MQTT(Supporting both Sunfull Cloud Platform IIOTSaaS and FanNeng ) server;

- Support MQTT server, Upload cloud server;

- Support personal WeChat Alarm, enterprise WeChat Alarm, DingTalk Alarm, MQTT server (supporting Sunfull Cloud platform and FanNeng Cloud platform), project upload cloud and other functions;

- Support JS script and PLC editing to realize logical control;

- Support user group management, timer, trigger;

- Support Web browsing and real-time data monitoring;

- Support Chinese name and description;
- X2View software is easy configuration, with 512 points configurable within 15minutes.

 

 

 

 

HMI1011-MBus Application Principle Diagram

 

 

Product Dimensions

 

 

 Download file list
Available Protocols List.pdf
HMI2004-A9-Instruction for installation.pdf
X2View-En.pdf(User Manual)
BTL_Cert_30342_ShanghaiSu_SunFullBAC.pdf

 

If you need to develop a non-standard protocol , please contact us.

If it is best to express the device to our company, the development cycle is usually 2 weeks.